(Note 1) Control input terminals (ST-F - RESET) and multifunction input terminals (MI1 - MI6) can also be arranged to GND common input (sink input). In this case, remove jumper pin on VFC2001 P.C.Board from [CN SO] and fit to [CN SI]. (Standard factory default setting is PS common input (source input).)
(Note 2) PG is used VF64V(vector control with speed sensor) mode only.
(Note 3) Never connect GND, COM terminal of control circuit with earth.
(Note 4) AC power source terminal (MR,MT) for control circuit is equipped in the Inverter of 1122, 1144 or over. (It is unnecessary to connect with power source ordinary. It is connected only when control circuit power source is required to turn on, such as execution of protection display)
(Note 5) Terminals + 1 and + 2 of Inverters of less than 1122 in 200V class and 1544 in 400V class are shorted. (in case of without DCL)
(Note 6) When thermal relay of dynamic resistor (DBR) tripped, break Inverter input.
(Note 7) Mount main circuit connector (52M) in accordance with use condition of customer.
(Note 8) Please wait from turning off to the re-turning on for ten minutes or more when you set up the main circuit contactor(52M) on the input side of the inverter.